在自然界中,水的来源是有多种多样,水对于不同的应用有不同的分析指标和意义。
在工业循环冷却水系统处理方面,我们针对补充水的水质主要是要判断其是属于结垢型水质还是腐蚀型水质,形成了三个主要的判断指数:朗格利尔(Langelier)饱和指数(L.S.I)、雷兹纳(Ryznar)稳定指数(R.S.I.)、帕科拉兹(Puckorius)结垢指数(P.S.I.)等。
表一 SYWATER ™ Circullating-water 指数分类
状态 | L.S.I=pH(实际)-pHs | R.S.I= 2pHs- pH(实际) | P.S.I= 2pHs- pHeq |
结垢 | 当L.S.I>0时 | 当R.S.I<6时 | 当P.S.I<6时 |
稳定 | 当L.S.I=0时 | 当R.S.I=6时 | 当P.S.I=6时 |
腐蚀 | 当L.S.I<0时 | 当R.S.I>6时 | 当P.S.I>6时 |
表二 SYWATER ™ Circullating-water 三指数对照表
结垢指数PSI | 稳定指数RSI | 饱和指数LSI | 状态 |
P.S.I.﹥9.2 | R.S.I.﹥9.1 | L.S.I.﹤-3.0 | 极易腐蚀 |
P.S.I.=8.2~9.2 | R.S.I.=8.1~9.1 | L.S.I.=-3.0~-2.5 | 严重腐蚀 |
P.S.I.=7.3~8.2 | R.S.I.=7.2~8.1 | L.S.I.=-1.5~-0.5 | 腐蚀 |
P.S.I.=6.2~7.3 | R.S.I.=6.1~7.2 | L.S.I.=-2.5~-1.5 | 轻微腐蚀 |
P.S.I.=5.8~6.2 | R.S.I.=5.7~6.1 | L.S.I.=-0.5~0.5 | 水质稳定 |
P.S.I.=4.8~5.8 | R.S.I.=4.7~5.7 | L.S.I.=0.5~1.5 | 轻微结垢 |
P.S.I.=3.8~4.8 | R.S.I.=3.7~4.7 | L.S.I.=1.5~2.5 | 结垢 |
P.S.I.=2.8~3.8 | R.S.I.=2.7~3.7 | L.S.I.=2.5~3.0 | 严重结垢 |
P.S.I.﹤2.8 | R.S.I.﹤2.7 | L.S.I.﹥3 | 极易结垢 |
LSI是从热力学平衡角度出发,在工程实际应用中有很大的局限,特别是循环水系统中投加水处理药剂后,根本失去预测作用,所以经常出现预测错误,稳定指数相对饱和指数更能准确预测水质,后期通过理论和几百个循环水系统经验计算,水中总碱度比水的实际Ph值更能正确的反映冷却水的腐蚀和结垢趋势,将稳定指数RSI实际测定的PH值改为平衡PH,即结垢指数更加切合实际生产。
为了更能精准预测循环水系统浓缩倍数等运行状况指标,上远环保集合总部技术人员、应用技术部人员、研发人员、网络部人员等设计研发了循环水“SYWATER Circullating-water 水质分析软件”,对补水水质的饱和LSI、结垢PSI、稳定RSI指数可进行精准分析,可快速获取该补水水质的各大指标,以及可***控制范围,为循环水精准控制提供了可靠的技术保证。